Free Electrical Work Permit (Enhanced) template for oil & gas you can edit online and download as PDF. Covers permit information, work team, electrical hazard identification & risk assessment.
PERMIT NO: ELEC-______________ PTW REFERENCE: PTW-______________
PROJECT/FACILITY: ______________ CONTRACTOR: ______________
WORK LOCATION: ______________ EQUIPMENT ID: ______________
EQUIPMENT DESCRIPTION: ______________
______________
WORK DESCRIPTION: ______________
______________
PERMIT VALIDITY: FROM: ______________ DATE: ______________ TO: ______________ DATE: ______________
(Electrical permits typically valid for ONE SHIFT only - maximum 12 hours)
WORK CLASSIFICATION: ☐ De-energized (Zero Energy State) ☐ Energized (Live Work) ☐ Verification Only
☐ Testing/Troubleshooting ☐ Inspection ☐ Maintenance
VOLTAGE LEVEL: ☐ Low Voltage (< 50V) ☐ Low Voltage (50V-600V) ☐ Medium Voltage (601V-15kV)
☐ High Voltage (15kV-69kV) ☐ Extra High Voltage (>69kV)
| ROLE | NAME | CERTIFICATION / LICENSE | ||
|---|---|---|---|---|
| Permit Applicant Authorized Electrician (In-charge) Licensed Electrical Worker Electrical Helper Safety Observer / Standby Person Operating Authority | ________ ________ ________ ________ ________ ________ | ________ License #: ______________ License #: ______________ Training Date: ___________ ________ ________ |
TOTAL NUMBER OF WORKERS: _____ (Minimum 2 persons for electrical work - buddy system)
Check all hazards applicable to this electrical work:
| PRIMARY ELECTRICAL HAZARDS: ☐ Electric shock / electrocution ☐ Arc flash burn ☐ Electrical fire ☐ Explosion (due to electrical fault) ☐ Secondary falls / injuries from shock ☐ Cardiac arrest / ventricular fibrillation | SHOCK/ARC FLASH HAZARDS: ☐ Arc flash / arc blast ☐ Arc flash boundary: ______ cal/cm² ☐ Incident energy level: ______ cal/cm² ☐ Arc flash PPE category: _____ ☐ Arc flash boundary distance: ______ m ☐ Limited approach boundary: ______ m ☐ Restricted approach boundary: ______ m ☐ Prohibited approach boundary: ______ m |
|---|---|
| WORK ACTIVITY HAZARDS: ☐ Working on live / energized equipment ☐ Lockout/Tagout (LOTO) isolation ☐ Testing / troubleshooting with power on ☐ Working near overhead power lines ☐ Working on underground cables ☐ Working in confined space (electrical) ☐ Working at height (electrical) ☐ Working in wet/damp conditions | EQUIPMENT-RELATED HAZARDS: ☐ Damaged insulation / cables ☐ Exposed conductors ☐ Moisture / water in equipment ☐ Corroded connections ☐ Overloaded circuits ☐ Faulty equipment / tools ☐ Improper grounding ☐ Static electricity accumulation |
| ENVIRONMENTAL HAZARDS: ☐ Flammable atmosphere present ☐ Combustible dust ☐ Poor lighting / visibility ☐ Confined workspace ☐ Extreme temperatures ☐ Noise >85dB | OTHER HAZARDS: ☐ Stored energy (capacitors, etc.) ☐ Backfeed / induced voltage ☐ Multiple power sources ☐ Interconnected systems ☐ Buried / concealed cables ☐ Other: ______________ |
ADDITIONAL HAZARD DETAILS: ______________
______________
EQUIPMENT DETAILS:
Equipment Name/ID: ______________ Panel/ MCC #: ______________
Nominal Voltage: ______________ V / ______________ kV
Available Fault Current: ______________ kA (if known)
ARC FLASH CALCULATIONS (if available):
Incident Energy: ______________ cal/cm² @ ______________ mm working distance
Arc Flash Boundary: ______________ mm / m
Arc Flash PPE Category: ☐ 0 ☐ 1 ☐ 2 ☐ 3 ☐ 4 (Based on NFPA 70E Table Method or Analysis)
Limited Approach Boundary (for shock): ______________ mm / m
Restricted Approach Boundary: ______________ mm / m
Prohibited Approach Boundary: ______________ mm / m
ARC FLASH LABEL AFFIXED TO EQUIPMENT? ☐ Yes ☐ No ☐ N/A
Label Information Verified? ☐ Yes ☐ No ☐ N/A (If No, explain: ______________)
RISK ASSESSMENT COMPLETED BY: ______________ DATE: ______________
(Qualified Electrical Engineer / Safety Professional)
WORK ACTIVITY TYPE:
☐ De-Energized Work (Zero Energy State Verified)
☐ Energized Work (Justified - see below)
☐ Testing / Troubleshooting (Temporarily Energized)
☐ Visual Inspection Only (No contact)
☐ Thermographic Inspection (Energized - Remote)
IF ENERGIZED WORK IS REQUIRED, JUSTIFICATION (NFPA 70E 130.2):
☐ De-energizing introduces additional or increased hazards
☐ De-energizing is infeasible due to equipment design or operational limitations
☐ Other: ______________
ENERGIZED WORK APPROVAL (Required for energized work >50V):
Approved by (Management/Supervisor): ______________ DATE: ______________
APPROACH BOUNDARIES FOR QUALIFIED PERSONS:
Work to be performed at:
☐ Outside Limited Boundary (No special PPE required)
☐ Within Limited Boundary (Shock protection training required)
☐ Within Restricted Boundary (Qualified person with PPE required)
☐ Within Prohibited Boundary (Same as contact - energized work)
ISOLATION POINTS:
| ENERGY SOURCE | ISOLATION TYPE | POINT ID | LOCK/TAG # | VERIFIED BY | ||
|---|---|---|---|---|---|---|
| Electrical Electrical Electrical Stored Energy Other: ______ | Breaker Disconnect MCC Bucket Capacitor ______ | ______ ______ ______ ______ ______ | #______ #______ #______ #______ #______ | ________ ________ ________ ________ ________ |
LOTO STATION / BOX #: ______________ NUMBER OF LOCKS APPLIED: ______________
GROUP LOTO PROCEDURE FOLLOWED? ☐ Yes ☐ No ☐ N/A
VERIFICATION OF ZERO ENERGY STATE:
Method of Verification:
☐ Voltage tester used (Model: ______________ Serial #: ______________)
☐ Voltage tester tested on known live source before use: ☐ Yes ☐ No
☐ Voltage tester tested after verification: ☐ Yes ☐ No
☐ Phase rotation/sequence verified (if required)
☐ Grounds applied (if required for high voltage)
TEST RESULTS:
Phase A to Ground: ______________ V Phase A to B: ______________ V
Phase B to Ground: ______________ V Phase B to C: ______________ V
Phase C to Ground: ______________ V Phase C to A: ______________ V
Neutral to Ground: ______________ V (if applicable)
VERIFIED ZERO ENERGY AT: ______________ (Time) BY: ______________ (Signature)
RE-VERIFICATION AFTER ANY INTERRUPTION:
Time: ______________ Verified by: ______________ Results: ☐ OK ☐ Not OK
| TEST EQUIPMENT & TOOLS: | STATUS | COMMENTS / CALIBRATION |
|---|---|---|
| Multimeter / Voltmeter Clamp Meter Insulation Tester (Megger) Phase Rotation Tester High Voltage Detector Live Line Tester Ground Tester | Good ☐ Fault ☐ Good ☐ Fault ☐ Good ☐ Fault ☐ Good ☐ Fault ☐ Good ☐ Fault ☐ Good ☐ Fault ☐ Good ☐ Fault ☐ | Calibration due: ______________ Calibration due: ______________ Calibration due: ______________ Calibration due: ______________ Tested: ______________ Tested: ______________ Calibration due: ______________ |
| HAND TOOLS: | STATUS | COMMENTS |
| Insulated Screwdrivers (rated for voltage) Insulated Pliers / Cutters Insulated Wrenches / Sockets Insulated Knives / Cable Cutters Insulated Ladder (Type: _____) Rubber Mats / Insulating Blankets Grounding Cables / Clamps Shorting / Grounding Set | Good ☐ Fault ☐ Good ☐ Fault ☐ Good ☐ Fault ☐ Good ☐ Fault ☐ Good ☐ Fault ☐ Good ☐ Fault ☐ Good ☐ Fault ☐ Good ☐ Fault ☐ | Rating: ______________ V Rating: ______________ V Rating: ______________ V Rating: ______________ V Rating: ______________ Rating: ______________ V Size: ______________ AWG Rating: ______________ |
| SAFETY EQUIPMENT: | STATUS | COMMENTS |
| Danger / Warning Signs Barricades / Safety Tape Lockout / Tagout Devices Fire Extinguisher (CO2 / Dry Chemical) First Aid Kit Emergency Eye Wash Communication Radios | In Place ☐ In Place ☐ In Place ☐ Present ☐ Present ☐ Available ☐ Working ☐ | Quantity: ______________ Area demarcated: ☐ Yes ☐ No Locks: _____ Tags: _____ Type: ______________ Burn kit available: ☐ Yes ☐ No Location: ______________ Channel: ______________ |
EQUIPMENT INSPECTED BY: ______________ DATE: ______________ TIME: ______________
(Authorized Electrician)
SHOCK PROTECTION PPE (Based on Voltage):
☐ Rubber Insulating Gloves (Class: _____) (Max use voltage: _____ V)
Glove Test Date: ______________ Next Test Due: ______________
☐ Leather Protector Gloves (over rubber gloves)
☐ Rubber Sleeves (Class: _____) (if required)
☐ Insulating Mat / Platform (Rating: _____ V)
☐ Insulated Tools (Rating: _____ V)
☐ Face Shield (for shock protection)
☐ Safety Glasses / Goggles
☐ Hard Hat (Class: _____)
ARC FLASH PPE (Based on Incident Energy / Category):
ARC FLASH PPE CATEGORY: _____ (0, 1, 2, 3, or 4)
CATEGORY 0 (1.2 cal/cm² or less):
☐ Arc-rated long sleeve shirt and pants or coverall (minimum ATPV 1.2 cal/cm²)
☐ Arc-rated face shield (or arc flash suit hood)
☐ Arc-rated jacket, parka, or rainwear (if required)
☐ Hard hat
☐ Safety glasses
☐ Hearing protection
☐ Leather gloves
☐ Leather footwear
CATEGORY 1 (4 cal/cm²):
☐ Arc-rated shirt and pants (minimum ATPV 4 cal/cm²)
☐ Arc-rated face shield (or arc flash suit hood)
☐ Arc-rated jacket, parka, or rainwear (if required)
☐ Hard hat
☐ Safety glasses
☐ Hearing protection
☐ Leather gloves
☐ Leather footwear
CATEGORY 2 (8 cal/cm²):
☐ Arc-rated shirt and pants (minimum ATPV 8 cal/cm²)
☐ Arc-rated flash suit hood OR arc-rated face shield + balaclava
☐ Arc-rated jacket, parka, or rainwear (if required)
☐ Hard hat
☐ Safety glasses
☐ Hearing protection
☐ Leather gloves
☐ Leather footwear
CATEGORY 3 (25 cal/cm²):
☐ Arc-rated shirt and pants (minimum ATPV 25 cal/cm²) OR arc-rated coverall
☐ Arc-rated flash suit hood
☐ Arc-rated jacket, parka, or rainwear (if required)
☐ Hard hat
☐ Safety glasses
☐ Hearing protection
☐ Leather gloves
☐ Leather footwear
CATEGORY 4 (40 cal/cm²):
☐ Arc-rated shirt and pants (minimum ATPV 40 cal/cm²) OR arc-rated coverall
☐ Arc-rated flash suit hood
☐ Arc-rated jacket, parka, or rainwear (if required)
☐ Hard hat
☐ Safety glasses
☐ Hearing protection
☐ Leather gloves (arc-rated)
☐ Leather footwear
PPE VERIFIED BY: ______________ DATE: ______________ TIME: ______________
(Qualified Person / Safety Representative)
| ITEM | YES | NO | N/A | INITIALS | COMMENTS |
|---|---|---|---|---|---|
| Work scope clearly defined and understood Hazard assessment completed Arc flash / shock risk assessment completed Energized work justification approved (if applicable) LOTO isolation points identified LOTO applied and verified Zero energy state verified (tested) Voltage tester verified on known source Grounds applied (if required) Test equipment calibrated and functioning Insulated tools available and rated for voltage Rubber gloves inspected and within test date Arc flash PPE available and correct for category Barricades / warning signs in place Work area clean and dry Adequate lighting available Fire extinguisher (appropriate type) available Emergency procedures reviewed Communication system tested and working Qualified electrical workers assigned and briefed Safety observer / standby person assigned and briefed Adjacent energized equipment identified and protected Other permits required (Confined Space, Hot Work, etc.) | ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ | ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ | ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ ☐ | ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ ______ | ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ Test date: _________ Category: _____ ________ ________ ________ Type: _________ ________ Channel: _____ ________ ________ ________ Permit #: _________ |
PRE-WORK CHECKLIST COMPLETED BY (Authorized Electrician): ______________ DATE: ______________
Justification for Energized Work (Must meet one of the following):
☐ De-energizing would introduce additional or increased hazards (specify):
______________
☐ De-energizing is infeasible due to equipment design or operational limitations (specify):
______________
☐ Other approved justification: ______________
SAFE WORK PRACTICES FOR ENERGIZED WORK:
☐ Energized work plan / procedure developed
☐ Detailed step-by-step work sequence established
☐ Approach boundaries established and respected
☐ Insulated tools and equipment used
☐ Rubber insulating gloves and sleeves worn
☐ Arc flash PPE as per category worn
☐ Barricades and warning signs in place
☐ Safety observer / standby person present
☐ Emergency response plan specific to energized work
☐ Work limited to qualified persons only
ENERGIZED WORK APPROVALS:
Electrical Supervisor: ______________ Date: ______________
Safety Manager: ______________ Date: ______________
Facility/Operations Manager: ______________ Date: ______________
Site Director/Manager (for >600V): ______________ Date: ______________
TOPICS COVERED:
☐ Scope of work ☐ Electrical hazards identified
☐ Voltage levels & boundaries ☐ Arc flash / shock PPE requirements
☐ LOTO isolation points & verification ☐ Energized work procedures (if applicable)
☐ Approach boundaries ☐ Emergency procedures
☐ Communication methods ☐ Stop work authority
☐ First aid / CPR / AED availability ☐ Emergency contacts
ATTENDEES:
| NAME | ROLE | COMPANY | SIGNATURE | ||
|---|---|---|---|---|---|
| ________ ________ ________ ________ ________ ________ | ________ ________ ________ ________ ________ ________ | ________ ________ ________ ________ ________ ________ | ________ ________ ________ ________ ________ ________ |
BRIEFING CONDUCTED BY: ______________ DATE: ______________ TIME: ______________
WORK START TIME: ______________ DATE: ______________
WORK ACTIVITY LOG:
| TIME | ACTIVITY / OBSERVATION | INITIALS | ||
|---|---|---|---|---|
| ______ ______ ______ ______ ______ ______ | ________ ________ ________ ________ ________ ________ | _______ _______ _______ _______ _______ _______ |
WORK COMPLETION TIME: ______________ DATE: ______________
ANY ISSUES / OBSERVATIONS DURING WORK? ☐ No ☐ Yes (describe below):
______________
______________
WORK COMPLETED BY (Authorized Electrician): ______________ DATE: ______________
PERMIT APPLICANT / AUTHORIZED ELECTRICIAN (Confirms isolation complete, area prepared):
I confirm that electrical isolation has been completed and verified, all hazards assessed,
and appropriate PPE and controls are in place.
Signature: ______________ Date: ______________ Time: ______________
SAFETY OBSERVER / STANDBY PERSON (Confirms understanding of duties):
I understand my duties as safety observer and will remain alert for the duration of the work.
Signature: ______________ Date: ______________ Time: ______________
OPERATING AUTHORITY (Confirms equipment released for work):
I confirm that the equipment has been released for electrical work and LOTO applied.
Signature: ______________ Date: ______________ Time: ______________
SAFETY REPRESENTATIVE (If present):
I have observed preparations and confirm they meet safety requirements.
Signature: ______________ Date: ______________ Time: ______________
FINAL APPROVAL - PERMIT ISSUED BY (Site Manager / Electrical Supervisor):
Signature: ______________ Date: ______________ Time: ______________
PERMIT VALID FOR WORK BETWEEN: Start: ______________ Date: ______________ End: ______________ Date: ___________
WORK COMPLETED / SUSPENDED:
Date: ______________ Time: ______________
☐ Work completed as planned
☐ Work suspended (reason): ______________
☐ Work incomplete - carry over to next shift required
WORK AREA INSPECTION:
☐ All tools and equipment removed from work area
☐ All debris / materials cleared
☐ Work area clean and tidy
☐ All personnel accounted for
☐ Grounds / shorting devices removed (if applied)
☐ Voltage tester re-checked on known source
DE-ISOLATION & RE-ENERGIZATION CHECKLIST:
☐ All workers clear of equipment
☐ All panels / enclosures closed and secured
☐ All guards / covers replaced
☐ Area clear of tools and materials
☐ Visual inspection of equipment complete
☐ Insulation resistance tested (if required)
☐ Operating authority notified of completion
☐ LOTO devices removed (by person who applied them)
☐ LOTO station / box cleared
☐ Equipment ready for re-energization
RE-ENERGIZATION VERIFICATION:
Voltage present after re-energization: ☐ Yes ☐ No
Phase rotation / sequence verified: ☐ Yes ☐ No ☐ N/A
Equipment functioning correctly: ☐ Yes ☐ No (explain: ______________)
AUTHORIZED ELECTRICIAN DECLARATION:
I confirm that the work area is clear, all personnel are accounted for, and the equipment
is ready for re-energization / has been safely re-energized.
Signature: ______________ Date: ______________ Time: ______________
OPERATING AUTHORITY (Equipment handover acceptance):
I confirm that the equipment has been returned to service and is operating normally.
Signature: ______________ Date: ______________ Time: ______________
Any incidents, near misses, or unsafe conditions during this electrical work:
☐ No incidents/near misses
☐ Incident occurred (complete below)
☐ Near miss occurred (complete below)
☐ Unsafe condition observed (complete below)
DESCRIPTION: ______________
______________
______________
CORRECTIVE ACTIONS TAKEN: ______________
______________
REPORTED BY: ______________ Date: ______________ Time: ______________
REPORT NUMBER (if applicable): ______________
THIS PERMIT IS VALID ONLY FOR THE DATE AND TIME SPECIFIED - ONE SHIFT ONLY
ALL CONDITIONS MUST BE RE-VERIFIED IF WORK IS NOT COMPLETED